Item No.: LY1-12.5/2(S)

LY1-12.5/2(S)PLUGGABLE SINGLE-POLE SPD

Description:

Classl·Classl·Type 1.Type 2
Location of Use: Main Distribution Boards
Mode of Protection: L-PE, N-PE
Surge Ratings: limp= up to 12.5 kA (10/350 μs)
I= up to 20 kA (8 /20 μs)
IEC/EN/UL Category: Class l+ll /Type 1+2
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance:lEC 61643-11:2011
EN 61643-11:2012
UL 1449 4th Edition

Quote Now

    Technical Data

    Internal Configuration

    Dimensions & Packaging

    Connection Diagram

    Electrical Characteristics
    SPD type 1+2+3
    Network 230/400 V 3-phase+N
    AC system TT-TNS
    Nominal line voltage Un 230/400 Vac
    Max. AC operating voltage Uc 275 Vac
    Temporary Over Voltage (TOV) Charasteristics – 5 sec. Without disconnection UT 335 Vac withstand
    Temporary Over Voltage (TOV) Charasteristics – 120 mn Without disconnection or with safety disconnection
    Temporary Over Voltage N/PE (TOV HT) Without disconnection or with safety disconnection UT 1.2 kV/300A/200 ms withstand
    Residual Current Leakage current to Ground Ipe None
    Follow current If None
    Nominal discharge current 15 x 8/20 µs impulses In 20 kA
    Max. discharge current max. withstand @ 8/20 µs by pole Imax 50 kA
    Impulse current by pole max. withstand 10/350µs by pole Iimp 12.5 kA
    Total lightning currentmax. total withstand @ 10/350µs Itotal 50 kA
    Withstand on Combination waveform IEC 61643-11 Class III test: 1.2/50µs – 8/20µs Uoc 6 kV
    Withstand on overvoltages IEEE C62.41.1 20 kV
    Specific energy by pole max. withstand 10/350 µs W/R 40 kJ/ohm
    Connection mode(s) L/N and N/PE
    Protection mode(s) Common/Differential mode
    Protection level L/N @ In (8/20µs) Up L/N 1.5 kV
    Protection level L/PE @ In (8/20µs) Up L/PE 1.5 kV
    Residual voltage L/N at 5 kA @ 5 kA (8/20µs) Up-5kA 0.7 kV
    Mechanical Characteristics
    Technology VG Technology (MOV+GSG)
    SPD configuration 3-phase+Neutral
    Connection to Network By 40mm busbar and wire for PE: 6-35mm² (50mm²)
    Format Plug-in modular box
    Mounting 40 mm busbar systems
    Housing material Thermoplastic UL94 V-0
    Operating temperature Tu -40/+85°C
    Outdoor application IP20
    Failsafe modem No
    Disconnection indicator Disconnection from AC network
    Remote signaling of disconnection 1 mechanical indicator by pole
    Dimensions Yes
    Weight See diagram
    Disconnectors 0.7401 kg
    Thermal disconnector Internal
    Installation ground fault breaker Type ‘S’ or delayed
    Fuses max. 315 A (gL/gG)
    Standards
    Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.

    Start Customizing Now

    We offer a full range of customised services, working closely with our customers every step of the way, from concept design to final delivery.

    Other&Products

    Our team is always guided by the needs of our customers, providing professional consultation and support to ensure your satisfaction.

    No results found.

    ANYTHING YOU COULDN’T FIND?

    Talk With Our Sales

    We know that every business is unique, so we offer customized services to ensure that our products perfectly match your specific needs:

    • Comprehensive brochure you can download
    • 15 years factory experience
    • Fast delivery
    • OEM&ODM
    • Low price
    • Small MQQ

    SEND US AN EMAIL

    devin@cnspd.com

    Contact Us

    We constantly evaluate and improve our processes to ensure that we are delivering the most efficient and reliable electrical products on the market.