LY1-12.5/2(S)PLUGGABLE SINGLE-POLE SPD
Description:
Classl·Classl·Type 1.Type 2
Location of Use: Main Distribution Boards
Mode of Protection: L-PE, N-PE
Surge Ratings: limp= up to 12.5 kA (10/350 μs)
I= up to 20 kA (8 /20 μs)
IEC/EN/UL Category: Class l+ll /Type 1+2
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance:lEC 61643-11:2011
EN 61643-11:2012
UL 1449 4th Edition
Electrical Characteristics | ||
SPD type 1+2+3 | ||
Network | 230/400 V 3-phase+N | |
AC system TT-TNS | ||
Nominal line voltage | Un | 230/400 Vac |
Max. AC operating voltage Uc 275 Vac | ||
Temporary Over Voltage (TOV) Charasteristics – 5 sec. Without disconnection | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics – 120 mn Without disconnection or with safety disconnection | ||
Temporary Over Voltage N/PE (TOV HT) Without disconnection or with safety disconnection | UT | 1.2 kV/300A/200 ms withstand |
Residual Current Leakage current to Ground Ipe None | ||
Follow current | If | None |
Nominal discharge current 15 x 8/20 µs impulses In 20 kA | ||
Max. discharge current max. withstand @ 8/20 µs by pole | Imax | 50 kA |
Impulse current by pole max. withstand 10/350µs by pole Iimp 12.5 kA | ||
Total lightning currentmax. total withstand @ 10/350µs | Itotal | 50 kA |
Withstand on Combination waveform IEC 61643-11 Class III test: 1.2/50µs – 8/20µs Uoc 6 kV | ||
Withstand on overvoltages IEEE C62.41.1 | 20 kV | |
Specific energy by pole max. withstand 10/350 µs W/R 40 kJ/ohm | ||
Connection mode(s) | L/N and N/PE | |
Protection mode(s) Common/Differential mode | ||
Protection level L/N @ In (8/20µs) | Up L/N | 1.5 kV |
Protection level L/PE @ In (8/20µs) Up L/PE 1.5 kV | ||
Residual voltage L/N at 5 kA @ 5 kA (8/20µs) | Up-5kA | 0.7 kV |
Mechanical Characteristics | ||
Technology | VG Technology (MOV+GSG) | |
SPD configuration | 3-phase+Neutral | |
Connection to Network | By 40mm busbar and wire for PE: 6-35mm² (50mm²) | |
Format | Plug-in modular box | |
Mounting | 40 mm busbar systems | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Outdoor application | IP20 | |
Failsafe modem | No | |
Disconnection indicator | Disconnection from AC network | |
Remote signaling of disconnection | 1 mechanical indicator by pole | |
Dimensions | Yes | |
Weight | See diagram | |
Disconnectors | 0.7401 kg | |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type ‘S’ or delayed | |
Fuses | max. 315 A (gL/gG) | |
Standards | ||
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Start Customizing Now
We offer a full range of customised services, working closely with our customers every step of the way, from concept design to final delivery.
Other&Products
Our team is always guided by the needs of our customers, providing professional consultation and support to ensure your satisfaction.
ANYTHING YOU COULDN’T FIND?
Talk With Our Sales
We know that every business is unique, so we offer customized services to ensure that our products perfectly match your specific needs:
- Comprehensive brochure you can download
- 15 years factory experience
- Fast delivery
- OEM&ODM
- Low price
- Small MQQ
SEND US AN EMAIL
Contact Us
We constantly evaluate and improve our processes to ensure that we are delivering the most efficient and reliable electrical products on the market.